LSB Series Air Cooled Chillers
Model No. Specification |
LSB- |
|||||||||
10AS |
12AS |
15AS |
20AS |
25AS |
30AS |
35AS |
40AS |
50AS |
||
Capty |
kW |
33.6 |
40.4 |
48.4 |
56.0 |
71.3 |
81.8 |
107 |
122.7 |
145 |
103kcal/hr |
28.9 |
34.7 |
41.6 |
48.2 |
61.3 |
70.3 |
92.0 |
105.5 |
124.7 |
|
Power(kW) |
8.4 |
10.0 |
11.7 |
14.3 |
18.0 |
21.5 |
26.5 |
32.2 |
39.4 |
|
current(A) |
15.0 |
18.1 |
20.9 |
27.3 |
34.8 |
40.5 |
49.8 |
59.0 |
75.6 |
|
Compr |
Qty(ps) |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
1 |
power(kW) |
7.23 |
8.84 |
10.3 |
12.63 |
15.8 |
18.68 |
23.7 |
28.0 |
35.2 |
|
current(A) |
12.65 |
15.8 |
17.95 |
21.9 |
27.2 |
32.50 |
41.8 |
50.3 |
66.9 |
|
Refriger ant |
type |
R22 |
||||||||
Control |
Thermal expansion valve |
|||||||||
Fan |
power(kW) |
1.2 |
1.2 |
1.4 |
1.7 |
2.2 |
2.8 |
2.8 |
4.2 |
4.2 |
current(A) |
2.3 |
2.3 |
2.9 |
5.4 |
7.6 |
8 |
8 |
8.7 |
8.7 |
|
Condr |
r pipe connection |
DN40 |
DN50 |
DN65 |
DN80 |
|||||
water flow(m3/h) |
7.0 |
8.5 |
10.1 |
11.8 |
15.0 |
17.3 |
22.5 |
25.9 |
31.0 |
|
Evapr |
water pipe connection(mm) |
DN40 |
DN50 |
DN65 |
DN80 |
|||||
water flow(m3/h) |
5.8 |
6.9 |
8.3 |
9.6 |
12.3 |
14.1 |
18.4 |
21.1 |
24.9 |
|
Overall size |
L(mm) |
1400 |
1420 |
1600 |
1900 |
1900 |
1900 |
2150 |
2150 |
2300 |
w(mm) |
800 |
800 |
850 |
900 |
900 |
900 |
1000 |
1000 |
1100 |
|
H(mm) |
1100 |
1100 |
1100 |
1250 |
1250 |
1300 |
1300 |
1350 |
1400 |
|
Weight |
kg |
330 |
400 |
550 |
700 |
800 |
900 |
950 |
1000 |
1100 |
Remark: 1.Designed condition:Chilled water in/out 12/7℃,cooling ;
2.Suitable chilled water temperature: 9~25℃;
3.Power supply:3P-380V-50Hz, voltage allowance:±10% voltage dif between the phase:±2%
4.The date above is for R22, contact us for R134a, R407C and other refrigerant
5.There may be change for improvement without notice, confirm always before your order
LSB Series Semi hermetic Chillers
Model No. Specification |
LSB- |
|||||||||
10WS |
12WS |
15WS |
20WS |
25WS |
30WS |
35WS |
40WS |
50WS |
||
Capty |
kW |
33.6 |
40.4 |
48.4 |
56.0 |
71.3 |
81.8 |
107 |
122.7 |
145 |
103kcal/hr |
28.9 |
34.7 |
41.6 |
48.2 |
61.3 |
70.3 |
92.0 |
105.5 |
124.7 |
|
Compr |
power(kW) |
7.23 |
8.84 |
10.3 |
12.63 |
15.8 |
18.68 |
23.7 |
28.0 |
35.2 |
current(A) |
12.65 |
15.8 |
17.95 |
21.9 |
27.2 |
32.50 |
41.8 |
50.3 |
66.9 |
|
Refriger ant |
type |
R22 |
||||||||
Control |
Thermal expansion valve |
|||||||||
Condr |
r pipe connection |
DN40 |
DN50 |
DN65 |
DN80 |
|||||
water flow(m3/h) |
8.0 |
9.7 |
11.4 |
13.4 |
16.9 |
19.7 |
25.6 |
29.8 |
36.4 |
|
Evapr |
r pipe connection |
DN40 |
DN50 |
DN65 |
DN80 |
|||||
water flow(m3/h) |
5.8 |
6.9 |
8.3 |
9.6 |
12.3 |
14.1 |
18.4 |
21.1 |
24.9 |
|
Overall size |
L(mm) |
1400 |
1420 |
1600 |
1900 |
1900 |
1900 |
2150 |
2150 |
2300 |
w(mm) |
800 |
800 |
850 |
900 |
900 |
900 |
1000 |
1000 |
1100 |
|
H(mm) |
1100 |
1100 |
1100 |
1250 |
1250 |
1300 |
1300 |
1350 |
1400 |
|
Weight |
kg |
330 |
400 |
550 |
700 |
800 |
900 |
950 |
1000 |
1100 |
Remark: 1.Designed condition:Chilled water in/out 12/7℃,cooling ;
2.Suitable chilled water temperature: 9~25℃;
3.Power supply:3P-380V-50Hz, voltage allowance:±10% voltage dif between the phase:±2%
4.The date above is for R22, contact us for R134a, R407C and other refrigerant
5.There may be change for improvement without notice, confirm always before your order
\