Refrigeration Equipment, cold room, cold storage
+86-13916430557
Home » MAC Series Air Coolers
Categories
News
Our newsletter
MAC Series Air Coolers
  • MAC Series Air Coolers
  • MAC Series Air Coolers
  • MAC Series Air Coolers

MAC Series Air Coolers

MAC series ceiling air cooler is Freon refrigeration units, can be used for the food fresh, cold storage and quick freezing etc.
Detailed description
 

MAC Series Air Coolers

Product Description and Features

MAC series ceiling air cooler is Freon refrigeration units, can be used for the food fresh, cold storage and quick freezing etc.

This series products features:

● Coil made of φ12.7 efficient copper tube with internal thread, 37.5×32.5 positioned in equilateral triangle.

● 4 different fin space of 4.0, 6.0, 8.5, 10.0 for customer’s choice to meet different temperature requirement of the room.

● External rotor fan for low temperature, with low noise, high efficiency, and reliability.

● Stainless steel electric heater produced by Italian Zuomoshi Company, which evenly placed in the coil with good defrosting effect.

● Fan motor and electric heater has been connected to the terminal box, convenient for wire connection.

● Shell made of alloy of aluminum or stainless plate, easy to be assembled and disassembled.  

Specification

Fin space 4.0mm (for room temperature 0℃and beyond)

Model

Nominal capacity

Area

Air flow

distance

Tube V

Fan motor

Defrosting electric heater tube

Voltage

Dia.

Qty.

Input

Voltage

Input (kW)

kW

m2

m3/h

m

dm3

V

mm

n

W

V

Coil tube

water

  φ350

MAC17/135HE

3.67

16.8

2500

12

4.0

380

350

1

150

220

1.2

0.6

MAC25/135HE

5.15

25.2

2300

11

6.0

380

350

1

150

220

1.2

0.6

MAC34/235HE

7.34

33.6

5000

13

7.7

380

350

2

300

220

2.4

1.2

MAC51/235HE

10.36

50.5

4600

12

11.5

380

350

2

300

220

3.6

1.2

MAC51/335HE

11.12

50.5

7500

14

11.3

380

350

3

450

220

3.0

1.5

MAC76/335HE

15.49

75.7

6900

13

17

380

350

3

450

220

4.5

1.5

φ450

MAC48/145HE

9.98

47.7

5000

14

11.1

380

450

1

250

220

3.3

1.3

MAC64/145HE

12.07

63.5

4800

12

14.7

380

450

1

250

220

4.4

1.3

MAC95/245HE

19.95

95.3

10000

16

21.4

380

450

2

500

220

6.0

2.4

MAC127/245HE

24.13

127

9600

14

28.5

380

450

2

500

220

8.0

2.4

MAC143/345HE

29.93

143

15000

18

31.8

380

450

3

750

220

9.0

3.3

MAC191/345HE

36.29

191

14400

16

42.4

380

450

3

750

220

12.0

3.3

MAC191/445HE

39.9

191

20000

18

42.1

380

450

4

1000

220

12.0

3.8

MAC254/445HE

48.26

254

19200

16

55

380

450

4

1000

220

16.0

3.8

φ550

MAC206/255HE

39.14

205.6

15600

20

45.8

380

550

2

1200

220

12

4

MAC257/255HE

46.48

257

15200

18

57.3

380

550

2

1200

220

16

4

MAC310/355HE

58.19

308.4

23400

22

68.2

380

550

3

1800

220

20

4

MAC385/355HE

69.71

385.4

22800

20

85.2

380

550

3

1800

220

24

4

MAC410/455HE

78.29

411

31200

23

90.6

380

550

4

2400

220

26

6

MAC514/455HE

93.05

514

30400

21

113.2

380

550

4

2400

220

30

6

φ630

MAC290/263HE

54.86

287.8

23600

30

64.2

380

630

2

1760

220

18

4.0

MAC360/263HE

65.05

359.7

21600

28

80.3

380

630

2

1760

220

24

4

MAC432/363HE

82.19

431.7

35400

30

95.5

380

630

3

2640

220

28

6

MAC540/363HE

97.62

539.6

32400

28

119

380

630

3

2640

220

35

6

MAC576/463HE

109.52

575.6

47200

30

127

380

630

4

3520

220

40

8

MAC720/463HE

130.2

719.5

43200

28

159

380

630

4

3520

220

50

8

Nominal capacity affected by: room temperature 0, evap. Temperature -8, different temperature DT=8K, and refrigerant is R22.

Fin space 6.0mm (for room temperature -18℃ and beyond)

Model

Nominal capacity

Area

Air flow

distance

Tube V

Fan motor

Defrosting electric heater tube

Voltage

Dia.

Qty.

Input

Voltage

Input (kW)

kW

m2

m3/h

m

dm3

V

mm

n

W

V

Coil tube

water

φ350

MAC12/135ME

2.95

11.5

2800

13

4.0

380

350

1

150

220

1.2

0.6

MAC17/135ME

4..11

17.3

2500

12

6.0

380

350

1

150

220

1.2

0.6

MAC23/235ME

5.9

23.0

5600

14

7.7

380

350

2

300

220

2.4

1.2

MAC35/235ME

8.22

34.6

5000

13

11.5

380

350

2

300

220

3.6

1.2

MAC35/335ME

8.87

34.6

8400

15

11.3

380

350

3

450

220

3.0

1.5

MAC52/335ME

12.35

51.9

7500

14

17

380

350

3

450

220

4.5

1.5

φ450

MAC33/145ME

7.26

32.6

5200

15

11.1

380

450

1

250

220

3.3

1.3

MAC44/145ME

8.68

43.5

5000

14

14.7

380

450

1

250

220

4.4

1.3

MAC65/245ME

14.54

65.2

10400

16

21.4

380

450

2

500

220

6.0

2.4

MAC87/245ME

17.39

87

10000

15

28.5

380

450

2

500

220

8.0

2.4

MAC98/345ME

21.95

98

15600

18

31.8

380

450

3

750

220

9.0

3.3

MAC131/345ME

26.03

130.6

15000

16

42.4

380

450

3

750

220

12.0

3.3

MAC131/445ME

29.17

130.6

20800

20

42.1

380

450

4

1000

220

12.0

3.8

MAC174/445ME

34.68

174

20000

18

55

380

450

4

1000

220

16.0

3.8

φ550

MAC141/255ME

30.1

140.8

16600

24

45.8

380

550

2

1200

220

12

4

MAC176/255ME

35.24

176

15600

22

57.3

380

550

2

1200

220

16

4

MAC210/355ME

4324

211.2

24900

26

68.2

380

550

3

1800

220

20

4

MAC264/355ME

52.76

264

23400

24

85.2

380

550

3

1800

220

24

4

MAC282/455ME

56.29

281.6

33200

28

90.6

380

550

4

2400

220

26

6

MAC352/455ME

70.38

352

31200

26

113.2

380

550

4

2400

220

30

6

φ630

MAC197/263ME

41.3

197.1

23600

28

64.2

380

630

2

1760

220

18

4.0

MAC246/263ME

49.24

246.4

21600

24

80.3

380

630

2

1760

220

24

4

MAC296/363ME

62

295.7

35400

30

95.5

380

630

3

2640

220

28

6

MAC370/363ME

73.9

369.6

32400

26

119

380

630

3

2640

220

35

6

MAC394/463ME

82.57

394.2

47200

30

127

380

630

4

3520

220

40

8

MAC493/463ME

98.57

492.8

43200

28

159

380

630

4

3520

220

50

8

Nominal capacity affected by: room temperature 0, evap. Temperature -8, different temperature DT=8K, and refrigerant is R22.

Fin space 8.5mm (for room temperature -25℃ and beyond)

Model

Nominal capacity

Area

Air flow

distance

Tube V

Fan motor

Defrosting electric heater tube

Voltage

Dia.

Qty.

Input

Voltage

Input (kW)

kW

m2

m3/h

m

dm3

V

mm

n

W

V

Coil tube

water

φ350

MAC9/135LE

2.47

8.6

3000

13

4.0

380

350

1

150

220

1.2

0.6

MAC13/135LE

3.33

13.0

2600

11

6.0

380

350

1

150

220

1.2

0.6

MAC17/235LE

4.94

17.3

6000

13

7.7

380

350

2

300

220

2.4

1.2

MAC26/235LE

6.65

25.9

5200

12

11.5

380

350

2

300

220

3.6

1.2

MAC26/335LE

7.32

25.9

9000

14

11.3

380

350

3

450

220

3.0

1.5

MAC39/335LE

9.98

38.9

7800

13

17

380

350

3

450

220

4.5

1.5

φ450

MAC25/145LE

6.27

24.5

5000

14

11.1

380

450

1

250

220

3.3

1.3

MAC33/145LE

7.79

32.6

4800

14

14.7

380

450

1

250

220

4.4

1.3

MAC50/245LE

12.54

49.5

10000

18

21.4

380

450

2

500

220

6.0

2.4

MAC65/245LE

15.49

65.2

9600

16

28.5

380

450

2

500

220

8.0

2.4

MAC74/345LE

18.81

73.5

15000

20

31.8

380

450

3

750

220

9.0

3.3

MAC98/345LE

23.28

98.0

14400

18

42.4

380

450

3

750

220

12.0

3.3

MAC98/445LE

25.18

98.0

20000

22

42.1

380

450

4

1000

220

12.0

3.8

MAC131/445LE

31.07

130.6

19200

20

55

380

450

4

1000

220

16.0

3.8

φ550

MAC106/255LE

25.14

105.6

16600

24

45.8

380

550

2

1200

220

12

4

MAC132/255LE

28.95

132.0

15600

22

57.3

380

550

2

1200

220

16

4

MAC160/355LE

37.7

158.4

24900

26

68.2

380

550

3

1800

220

20

4

MAC198/355LE

43.43

198.0

23400

24

85.2

380

550

3

1800

220

24

4

MAC210/455LE

50.29

211.2

33200

28

90.6

380

550

4

2400

220

26

6

MAC264/455LE

57.8

264.0

31200

26

113.2

380

550

4

2400

220

30

6

φ630

MAC150/263LE

35.24

147.8

23600

28

64.2

380

630

2

1760

220

18

4.0

MAC185/263LE

40.57

185.0

21600

24

80.3

380

630

2

1760

220

24

4

MAC222/363LE

52.86

221.8

35400

30

95.5

380

630

3

2640

220

28

6

MAC277/363LE

60.76

277.2

32400

26

119

380

630

3

2640

220

35

6

MAC296/463LE

70.38

295.7

47200

30

127

380

630

4

3520

220

40

8

MAC370/463LE

80.95

369.6

43200

28

159

380

630

4

3520

220

50

8

Nominal capacity affected by: room temperature 0, evap. Temperature -8, different temperature DT=8K, and refrigerant is R22.

Fin space 10.0mm (for room temperature -35℃and beyond)

Model

Nominal capacity

Area

Air flow

distance

Tube V

Fan motor

Defrosting electric heater tube

Voltage

Dia.

Qty.

Input

Voltage

Input (kW)

kW

m2

m3/h

m

dm3

V

mm

n

W

V

Coil tube

water

φ450

MAC21/145JE

5.8

21.2

5000

14

11.1

380

450

1

250

220

3.3

1.3

MAC28/145JE

7.22

28.3

4800

14

14.7

380

450

1

250

220

4.4

1.3

MAC43/245JE

11.69

42.4

10000

18

21.4

380

450

2

500

220

6.0

2.4

MAC57/245JE

14.54

56.6

9600

16

28.5

380

450

2

500

220

8.0

2.4

MAC64/345JE

17.48

63.6

15000

20

31.8

380

450

3

750

220

9.0

3.3

MAC85/345JE

21.85

85.0

14400

18

42.4

380

450

3

750

220

12.0

3.3

MAC85/445JE

23.47

85.0

20000

22

42.1

380

450

4

1000

220

12.0

3.8

MAC113/445JE

29.07

113.2

19200

20

55

380

450

4

1000

220

16.0

3.8

φ550

MAC92/255JE

25.24

91.5

16600

24

45.8

380

550

2

1200

220

12

4

MAC115/255JE

29.43

114.4

15600

22

57.3

380

550

2

1200

220

16

4

MAC140/355JE

37.9

137.3

24900

26

68.2

380

550

3

1800

220

20

4

MAC172/355JE

44.19

172

23400

24

85.2

380

550

3

1800

220

24

4

MAC183/455JE

50.57

183

33200

28

90.6

380

550

4

2400

220

26

6

MAC230/455JE

58.86

228.8

31200

26

113.2

380

550

4

2400

220

30

6

φ630

MAC130/263JE

35.3

128.1

23600

28

64.2

380

630

2

1760

220

18

4.0

MAC160/263JE

41.24

160.2

21600

24

80.3

380

630

2

1760

220

24

4

MAC192/363JE

53.05

192.2

35400

30

95.5

380

630

3

2640

220

28

6

MAC240/363JE

61.8

240.2

32400

26

119

380

630

3

2640

220

35

6

MAC256/463JE

70.76

256.3

47200

30

127

380

630

4

3520

220

40

8

MAC320/463JE

82.38

320.3

43200

28

159

380

630

4

3520

220

50

8

Nominal capacity affected by: room temperature 0, evap. Temperature -8, different temperature DT=8K, and refrigerant is R22.

Overall and installation size

Model

Overall size(mm)

Installation size (mm)

Pipe connection

(mm)

drainage

A

B

C

D

E

E1

E2

E3

F

Inlet

outlet

MAC17/135HE

MAC12/135ME

MAC9/135LE

885

460

575

430

635

122.5

φ12.7

φ22

1”

MAC25/135HE

MAC17/135ME

MAC13/135LE

885

460

575

430

635

122.5

φ12.7

φ22

1”

MAC34/235HE

MAC23/235ME

MAC17/235LE

1485

460

575

430

1235

122.5

φ12.7

φ28

1”

MAC51/235HE

MAC35/235ME

MAC26/235LE

1485

460

575

430

1235

122.5

φ12.7

φ28

1”

MAC51/335HE

MAC35/335ME

MAC26/335LE

2085

460

575

430

1835

122.5

φ12.7

φ28

2”

MAC76/335HE

MAC52/335ME

MAC39/335LE

2085

460

575

430

1835

122.5

φ16

φ35

2”

MAC48/145HE

MAC33/145ME

MAC25/145LE

MAC21/145JE

1205

600

730

575

890

155

φ22

φ35

1”

MAC64/145HE

MAC44/145ME

MAC33/145LE

MAC28/145JE

1205

600

730

575

890

155

φ22

φ35

1”

MAC95/245HE

MAC65/245ME

MAC50/245LE

MAC43/245JE

2055

600

730

575

1740

870

155

φ22

φ42

2”

MAC127/245HE

MAC87/245ME

MAC65/245LE

MAC57/245JE

2055

600

730

575

1740

870

155

φ22

φ42

2”

MAC143/345HE

MAC98/345ME

MAC74/345LE

MAC64/345JE

2905

600

730

575

2590

870

850

155

φ28

φ42

2-1”

MAC191/345HE

MAC131/345ME

MAC98/345LE

MAC85/345JE

2905

600

730

575

2590

870

850

155

φ28

φ42

2-1”

MAC191/445HE

MAC131/445ME

MAC98/445LE

MAC85/445JE

3755

600

730

575

3440

870

850

850

155

φ28

φ42

2”

MAC254/445HE

MAC174/445ME

MAC131/445LE

MAC113/445JE

3755

600

730

575

3440

870

850

850

155

φ28

φ54

2”

MAC206/255HE

MAC141/255ME

MAC106/255LE

MAC92/255JE

2577

715

890

615

2240

1120

1120

166

φ28

φ54

2-1”

MAC257/255HE

MAC176/255ME

MAC132/255LE

MAC115/255JE

2577

715

890

615

2240

1120

1120

166

φ28

φ54

2-1”

MAC310/355HE

MAC210/355ME

MAC160/355LE

MAC140/355JE

3677

715

890

615

3340

1120

1100

166

φ35

φ54

2-1”

MAC385/355HE

MAC264/355ME

MAC198/355LE

MAC172/355JE

3677

715

890

615

3340

1120

1100

166

φ35

φ54

2-1”

MAC410/455HE

MAC282/455ME

MAC210/455LE

MAC183/455JE

4777

715

890

615

4440

1120

1100

1100

166

2-φ28

2-φ54

2-2”

MAC514/455HE

MAC352/455ME

MAC264/455LE

MAC230/455JE

4777

715

890

615

4440

1120

1100

1100

166

2-φ28

2-φ54

2-2”

MAC290/263HE

MAC197/263ME

MAC150/263LE

MAC130/263JE

2577

775

1186

685

2240

1120

1120

166

φ28

φ54

2-1”

MAC360/263HE

MAC240/263ME

MAC185/263LE

MAC160/263JE

2577

775

1186

685

2240

1120

1120

166

φ28

φ54

2-1”

MAC430/363HE

MAC296/363ME

MAC222/363LE

MAC190/363JE

3677

775

1186

685

3340

1120

1100

166

φ35

φ54

2-1”

MAC540/363HE

MAC370/363ME

MAC277/363LE

MAC240/363JE

3677

775

1186

685

3340

1120

1100

166

φ35

φ54

2-1”

MAC576/463HE

MAC394/463ME

MAC296/463LE

MAC286/463JE

4777

775

1186

685

4440

1120

1100

1100

166

2-φ28

2-φ54

2-2”

MAC720/463HE

MAC493/463ME

MAC370/463LE

MAC320/463JE

4777

775

1186

685

4440

1120

1100

1100

166

2-φ28

2-φ54

2-2”

Mode Selection

  The capacity specified for the air coolers is nominal. The customer can choose the right model according to their applying condition, the refrigerant, temperature between, temperature differences etc. The real capacity can be got by the equation below:

QRQN×A1×A2

noteQR  ——  real capacity  (kW)

      QN  ——  nominal capacity  (kW)

      A1  ——  temperature coefficient    see table 1

      A2  ——  refrigerant coefficient      see table 2

Temperature coefficient A1 (table 1)

Heat transfer

 DT(℃)

Room temperature

 (℃)

8

5

4

3

2

1

0

-5

-10

-15

-20

-25

-30

-35

5

0.73

0.73

0.71

0.69

0.67

0.65

0.63

0.61

0.60

0.58

0.56

0.55

0.54

0.54

6

0.88

0.88

0.85

0.83

0.80

0.78

0.75

0.73

0.71

0.70

0.68

0.66

0.65

0.65

7

1.03

1.03

1.0

0.97

0.94

0.91

0.88

0.85

0.83

0.81

0.79

0.77

0.76

0.76

8

1.17

1.17

1.14

1.10

1.07

1.04

1.0

0.98

0.95

0.93

0.90

0.88

0.87

0.87

9

1.32

1.32

1.28

1.24

1.20

1.16

1.13

1.10

1.07

1.04

1.02

0.99

0.98

0.98

10

1.47

1.46

1.42

1.38

1.34

1.29

1.25

1.22

1.19

1.16

1.13

1.10

1.09

1.09

 (DT) = room temperature evaporation temperature

Refrigerant coefficient A2 (table 2)

refrigerant

Room temperature 

(℃)

8

5

4

3

2

1

0

-5

-10

-15

-20

-25

-30

-35

R22

1

1

1

1

1

1

1

1

1

1

1

1

1

1

R134a

0.98

0.97

0.97

0.97

0.96

0.96

0.96

0.94

0.93

0.91

-

-

-

-

R404A

1.05

1.05

1.05

1.05

1.05

1.05

1.05

1.05

1.05

1.05

1.05

1.05

1.05

1.05

Example:

 Air cooler for capacity 20KW, room temperature -25℃,evaporating temperature -32, refrigerant is R22.

Model Choose Steps:

1) Get heat transfer different temperature: DT=-25-(-32)= 7℃

2) According to DT= 7℃ and room temperature is -25℃, and get the temperature effect coefficient A1, check table 1, and see A1=0.77

3) Get refrigerant coefficient, check table 2, and see A2=1.

4) Get the nominal capacity:

     QNQR÷(A1×A2)20÷(0.77×1)= 25.97 ( KW)

5) Choose the model

For the room temperature is -25, choose the air cooler with 8.5 fin space, and as the 25.97kw nominal capacity, the model can be: MAC98/445LE.